DEK-OE- 24DC/ 48DC/100 – 2940207 – Solid-state Relay Terminal Block – Phoenix Contact Solid-state Relays And Electromechanical Relays
USD 59.80
Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.
Commercial Data
| Item number |
2940207 |
| Packing unit |
10 pc |
| Minimum order quantity |
1 pc |
| Product key |
DK61A1 |
| Catalog page |
Page 442 (C-5-2019) |
| GTIN |
4017918079901 |
| Weight per piece (including packing) |
20.83 g |
| Weight per piece (excluding packing) |
20.53 g |
| Customs tariff number |
85364190 |
| Country of origin |
CN |
Notes
| Note on application |
Use of EB 80-DIK… bridges in the DEK terminal blocks: Absorption of humidity from the ambient air as well as an unfavorable tolerance between a larger number of DEK terminal blocks and the EB 80-DIK… bridge may cause (minor) expansion of the DEK housing. When the EB 80-DIK… bridges are used, therefore, it is recommended that these be disconnected after about 10 to 12 DEK terminal blocks and a wire bridge to the next DEK terminal block be inserted in their place. |
Product Properties
| Product type |
Solid-state relay module |
| Product family |
DEK |
| Application |
Output function |
| Operating mode |
100% operating factor |
| Insulation characteristics: Standards/regulations |
| Insulation |
Basic insulation |
| Overvoltage category |
III |
| Pollution degree |
2 |
| Data management status |
| Date of last data management |
17.01.2025 |
Electrical Properties
| Maximum power dissipation for nominal condition |
10 mW |
| Test voltage (Input/output) |
2.5 kV AC (Input/output) |
Input Data
| Nominal input voltage UN |
24 V DC |
| Input voltage range in reference to UN |
0.8 … 1.2 |
| Input voltage range |
19.2 V DC … 28.8 V DC |
| Switching threshold “0” signal in reference to UN |
≤ 0.4 |
| Switching threshold “1” signal in reference to UN |
≥ 0.8 |
| Typical input current at UN |
7 mA |
| Typical response time |
20 µs |
| Typical turn-off time |
200 µs |
| Operating voltage display |
Green LED |
| Protective circuit |
Reverse polarity protection |
| Transmission frequency |
300 Hz |
Output Data
| Contact switching type |
1 N/O contact |
| Design of digital output |
electronic |
| Output voltage range |
3 V DC … 48 V DC |
| Limiting continuous current |
100 mA |
| Voltage drop at max. limiting continuous current |
≤ 0.9 V |
| Output circuit |
2-conductor floating, 3-conductor ground-referenced |
| Protective circuit |
Reverse polarity protection; Polarity protection diode |
| Freewheeling diode; Freewheeling diode |
| Output resistor |
approx. 22 kΩ (for 3-conductor operation) |
Connection Data
| Connection method |
Screw connection |
| Stripping length |
8 mm |
| Screw thread |
M3 |
| Conductor cross section rigid |
0.2 mm² … 2.5 mm² |
| Conductor cross section flexible |
0.2 mm² … 2.5 mm² |
| Conductor cross section AWG |
24 … 14 |
| Tightening torque |
0.5 Nm |
Dimension
| Width |
6.2 mm |
| Height |
80 mm |
| Depth |
56 mm |
Material Specifications
Environmental and real-life conditions
| Ambient conditions |
| Ambient temperature (operation) |
-20 °C … 60 °C |
| Ambient temperature (storage/transport) |
-40 °C … 70 °C |
Standards And Regulations
| Standards/regulations |
| Standards/regulations |
IEC 60947-5-1 |
Mounting
| Mounting type |
DIN rail mounting |
| Assembly note |
in rows with zero spacing |
| Mounting position |
any |