Siemens SIRIUS 3RV1 Motor Protection Circuit Breaker

USD 74.63

3-pole motor protection circuit breaker, Class 10, with 5.5-8A overload and 104A short-circuit release for 690V applications.

SKU Siemens-3RV1011-1HA10 Category
Top Brands > Siemens > Siemens Motor Starter Protectors

Siemens SIRIUS 3RV1 Motor Protection Circuit Breaker

Model Identifier 3RV1011
Official Part Number 3RV1011-1HA10
GTIN Standard 4011209263680

Technical Overview

3-pole motor protection circuit breaker, Class 10, with 5.5-8A overload and 104A short-circuit release for 690V applications.

Key Features

  • Designed for motor protection applications.
  • Adjustable thermal overload release (A-release) from 5.5 to 8 A.
  • Fixed magnetic instantaneous short-circuit release (N-release) at 104 A.
  • Compact size S00.
  • CLASS 10 trip characteristic for standard motor protection.
  • Equipped with screw terminals for secure electrical connection.
  • Suitable for DIN rail mounting.
  • 3-pole configuration for main current circuits.

Reliable motor protection with integrated overload and short-circuit release functionality.

Technical Specification Matrix

ParameterValue
Circuit Breaker SizeS00
Motor Protection ClassCLASS 10
Adjustable Overload Release Current (A-release)5.5 - 8 A
Instantaneous Short-Circuit Release Current (N-release)104 A
Rated Operating Voltage690 V AC
Insulation Voltage Rated Value (degree of pollution 3, AC)690 V
Surge Voltage Resistance Rated Value6 kV
Protection Class IP (on the front)IP20
Protection Class IP (of the terminal)IP00
Ambient Temperature during Operation-20 ... +60 °C
Ambient Temperature during Storage-50 ... +80 °C
Mounting TypeScrew and snap-on mounting onto 35 mm DIN rail
Electrical Connection TypeScrew-type terminals
Number of Poles for Main Current Circuit3
Rated Continuous Current8 A
Power Loss (AC in hot operating state)9.25 W
Mechanical Service Life (main contacts typical)100,000 operating cycles
Electrical Endurance (typical)100,000 operating cycles
Short-Circuit Breaking Capacity (Icu) at 400 V AC50 kA
Short-Circuit Breaking Capacity (Icu) at 240 V AC100 kA
Short-Circuit Breaking Capacity (Icu) at 500 V AC3 kA
Short-Circuit Breaking Capacity (Icu) at 690 V AC2 kA
Physical Weight (kg)0.2556
Dimensions L x W x H (cm)10 x 4.9 x 8.4

Industrial Applications

1. Small Motor Protection in HVAC Systems

This circuit breaker can be used to protect small fan motors or pump motors in commercial and industrial HVAC (Heating, Ventilation, and Air Conditioning) systems, ensuring reliable operation.

Problem Solved

Prevents motor damage due to overloads from seized bearings or duct obstructions (thermal overload 5.5-8A) and safeguards against catastrophic failures from short circuits (magnetic trip 104A) in 3-phase systems up to 690V. The Class 10 trip ensures quick reaction to protect motors in typical starting conditions.

Motor protectionHVACFan motorPump motorOverloadShort-circuit3-phase690VClass 10

2. Conveyor Belt Drive Motor Protection

Ideal for protecting the 3-phase electric motors driving small to medium-sized conveyor belts in manufacturing or logistics facilities, maintaining operational safety.

Problem Solved

Protects the motor from sustained overcurrents caused by conveyor jams or excessive load (5.5-8A adjustable thermal release) and provides rapid shutdown during severe electrical faults like short circuits (104A magnetic release), ensuring operational safety and extending motor life in an industrial environment up to 60°C.

Conveyor systemDrive motorManufacturingLogisticsOverload protectionShort-circuit protection3-phaseClass 105.5-8A104AIndustrial

3. Industrial Pump Motor Protection for Water Treatment

Suitable for protecting 3-phase pump motors in water treatment plants or chemical dosing systems, handling water or non-corrosive liquids, crucial for continuous process operation.

Problem Solved

Offers reliable thermal overload protection (5.5-8A) against issues like dry running or clogged pipes, and magnetic short-circuit protection (104A) against electrical faults, which are critical for maintaining continuous operation and preventing costly downtime in process industries. Its 690V rating and IP20 (front) protection are adequate for typical indoor control panel installations.

Water treatmentPump motorChemical dosingOverloadShort circuitProcess control3-phase690VClass 10IP20Industrial panel