$ 227.24
Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.
| Item number | 2905577 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Product key | DK1132 | 
| Catalog page | Page 100 (C-7-2015) | 
| GTIN | 4046356966290 | 
| Weight per piece (including packing) | 87.7 g | 
| Weight per piece (excluding packing) | 87.7 g | 
| Customs tariff number | 85437090 | 
| Country of origin | DE | 
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer’s declaration in the download area | 
| Product type | Repeater power supply | 
| Product family | MINI Analog | 
| No. of channels | 1 | 
| Insulation characteristics | |
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Electrical isolation | 3-way isolation | 
| Limit frequency (3 dB) | > 175 Hz | 
| Protective circuit | Transient protection | 
| Signal transmission behavior | In = Out | 
| Step response (10-90%) | < 2 ms | 
| Maximum temperature coefficient | < 0.01 %/K | 
| Temperature coefficient, typical | < 0.01 %/K | 
| Maximum transmission error | ≤ 0.1 % (of final value) | 
| Electrical isolation Input/output/power supply | |
| Rated insulation voltage | 50 V AC/DC | 
| Test voltage | 1.5 kV AC (50 Hz, 60 s) | 
| Insulation | Basic insulation in accordance with IEC/EN 61010 | 
| Supply | |
| Nominal supply voltage | 24 V DC | 
| Supply voltage range | 19.2 V DC … 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) | 
| Power consumption | < 600 mW (at 24 V DC) | 
| Signal | |
| Number of inputs | 1 | 
| Current input signal | 0 mA … 20 mA | 
| 4 mA … 20 mA | |
| Max. current input signal | 20 mA | 
| Input voltage limitation | < 2 V (20 mA) | 
| Signal: Current | |
| Number of outputs | 1 | 
| Current output signal | 0 mA … 20 mA | 
| 4 mA … 20 mA | |
| Load/output load current output | ≤ 800 Ω (at 20 mA) | 
| Ripple | < 20 mVrms | 
| Connection method | Screw connection | 
| Stripping length | 12 mm | 
| Screw thread | M3 | 
| Conductor cross section rigid | 0.2 mm² … 2.5 mm² | 
| Conductor cross section flexible | 0.2 mm² … 2.5 mm² | 
| Conductor cross section AWG | 26 … 12 | 
| Data communication (bypass) | |
| HART function | Yes | 
| Limit frequency (3 dB) | 2.5 Hz | 
| Width | 6.2 mm | 
| Height | 93.1 mm | 
| Depth | 101.2 mm | 
| Color | green (RAL 6021) | 
| Housing material | PBT | 
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 2 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 2 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 2 | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -20 °C … 60 °C | 
| Ambient temperature (storage/transport) | -40 °C … 85 °C | 
| Altitude | ≤ 2000 m | 
| Permissible humidity (operation) | 5 % … 95 % (non-condensing) | 
| CE | |
| Certificate | CE-compliant | 
| UKCA | |
| Certificate | UKCA-compliant | 
| UL, USA/Canada | |
| Identification | UL 508 Listed | 
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Class I, Zone 2, Group IIC | |
| Shipbuilding approval | |
| Certificate | DNV GL TAA000020N | 
| Shipbuilding data | |
| Temperature | B | 
| Humidity | B | 
| Vibration | B | 
| EMC | A | 
| Enclosure | Required protection according to the Rules shall be provided upon installation on board | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Noise immunity | EN 61000-6-2 | 
| Note | When being exposed to interference, there may be minimal deviations. | 
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Electrostatic discharge | |
| Standards/regulations | EN 61000-4-2 | 
| Electrostatic discharge | |
| Comments | Safety measures must be taken to prevent electrostatic discharge. | 
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field | 
| Standards/regulations | EN 61000-4-3 | 
| Typical deviation from the measuring range final value | 3 % | 
| Fast transients (burst) | |
| Designation | Fast transients (burst) | 
| Standards/regulations | EN 61000-4-4 | 
| Typical deviation from the measuring range final value | 3 % | 
| Surge current load (surge) | |
| Standards/regulations | EN 61000-4-5 | 
| Surge current load (surge) | |
| Comments | Criterion B | 
| Conducted interference | |
| Designation | Conducted interferences | 
| Standards/regulations | EN 61000-4-6 | 
| Typical deviation from the measuring range final value | 3 % | 
| Electrical isolation | 3-way isolation | 
| Mounting type | DIN rail mounting | 
| Assembly note | The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715. | 
| Mounting position | any |