EasyPact TVS – LRE – Type E 3 Poles Thermal Overload Relay – Schneider Thermal Overload Relays
$ 74.80 – $ 370.48
SKU: N/A
Specifications
Main | |||
Part Number | LRE482N | LRE483N | LRE484N |
Product Series | Compact | Compact | Compact |
product name | EasyPact TVS | EasyPact TVS | EasyPact TVS |
product type | Type E 3 pole thermal overload relay | Type E 3 pole thermal overload relay | Type E 3 pole thermal overload relay |
product short name | LRE | LRE | LRE |
Relay application | Motor protection | Motor protection | Motor protection |
phase loss sensitivity | 1.3 Ir on two phases, 0 on the other phase conforming to IEC 60947-4-1 | 1.3 Ir on two phases, 0 on the other phase conforming to IEC 60947-4-1 | 1.3 Ir on two phases, 0 on the other phase conforming to IEC 60947-4-1 |
Additional information | |||
The scope of products | LC1E120…630 | LC1E160…630 | LC1E200…630 |
Network Type | AC | AC | AC |
operating frequency | 50/60Hz | 50/60Hz | 50/60Hz |
installation method | Mounting on the bottom plate of the contactor, with special accessories |
Mounting on the bottom plate of the contactor , with special accessories |
Mounting on the bottom plate of the contactor , with special accessories |
Thermal release drag rating | Class 10A conforming to IEC 60947-4-1 | Class 10A conforming to IEC 60947-4-1 | Class 10A conforming to IEC 60947-4-1 |
Signal indication function | Relay Trip Indicator | Relay Trip Indicator | Relay Trip Indicator |
Relay setting range | 84…135A | 124…198A | 146…234A |
Trip threshold | 1.14 ± 0.06 In conforming to IEC 60947-4-1 | 1.14 ± 0.06 In conforming to IEC 60947-4-1 | 1.14 ± 0.06 In conforming to IEC 60947-4-1 |
Conventional thermal current [Ith] | 5 A for control circuits | 5 A for control circuits | 5 A for control circuits |
Rated working voltage [Ue] | <= 690V AC | <= 690V AC | <= 690V AC |
Fuses for use with relays | 5 A gG for control circuits 200 A gG for power circuits 160 A aM for power circuits |
5 A gG for control circuits 250 A gG for power circuits 200 A aM for power circuits |
5 A gG for control circuit 315 A gG for power circuit 250 A aM for power circuit |
Rated insulation voltage [Ui] | 690 V conforming to IEC 60947-4-1 | 690 V conforming to IEC 60947-4-1 | 690 V conforming to IEC 60947-4-1 |
Rated impulse withstand voltage [Uimp] | 6kV | 6kV | 6kV |
control type | Stop: Red (push) button Reset: Green (push) button |
Stop: Red (push) button Reset: Green (push) button |
Stop: Red (push) button Reset: Green (push) button |
Temperature compensation | -20…60°C | -20…60°C | -20…60°C |
Phase spacing | 34.8 mm | 40 mm | 48 mm |
Wiring capacity | Terminal busbar cross-section: 3 x 18 mm | Terminal busbar cross-section: 3 x 20 mm | Terminal busbar cross-section: 3 x 25 mm |
Tightening torque | 27.5 Nm Via lug screw: M8 | 27.5 Nm Via lug screw: M8 | 35 Nm via lug screw: M10 |
high | 141 mm | 131 mm | 134 mm |
width | 180 mm | 180mm | 180 mm |
depth | 134 mm | 134 mm | 134 mm |
Product Weight | 1.67kg | 1.67kg | 1.67kg |
environment | |||
Standards compliant | IEC 60947-4-1 GB 14048 |
IEC 60947-4-1 GB 14048 |
GB 14048 IEC 60947-4-1 |
certified product | CCC | CCC | CCC |
Protective measures | TH conforms to IEC 60068 | TH conforms to IEC 60068 | TH conforms to IEC 60068 |
IP protection class | IP00 conforming to IEC 60529 | IP00 conforming to IEC 60529 | IP00 conforming to IEC 60529 |
ambient temperature | -20…60 °C without derating according to IEC 60947-4-1 -20…70 °C with derating |
-20…60 °C without derating according to IEC 60947-4-1 -20…70 °C with derating |
-20…60 °C without derating according to IEC 60947-4-1 -20…70 °C with derating |
storage environment temperature | -60…80°C | -60…80°C | -60…80°C |
Fire resistance and abnormal high temperature resistance | 850 °C conforming to IEC 60068-2-1 | 850 °C conforming to IEC 60068-2-1 | 850 °C conforming to IEC 60068-2-1 |
Shock and vibration resistance | Shock resistance: 6 gn (11ms) conforming to IEC 60068-2-7 Shock resistance: 6 gn conforming to IEC 60068-2-6 |
Shock resistance: 6 gn (11ms) conforming to IEC 60068-2-7 Shock resistance: 6 gn conforming to IEC 60068-2-6 |
Shock resistance: 6 gn (11ms) conforming to IEC 60068-2-7 Shock resistance: 6 gn conforming to IEC 60068-2-6 |
Insulation properties | 6 kV at 50 Hz conforming to IEC 60255-5 | 6 kV at 50 Hz conforming to IEC 60255-5 | 6 kV at 50 Hz conforming to IEC 60255-5 |
electromagnetic compatibility | Impulse withstand voltage: 6 kV conforming to IEC 60801-5 | Impulse withstand voltage: 6 kV conforming to IEC 60801-5 | Impulse withstand voltage: 6 kV conforming to IEC 60801-5 |
packaging unit | |||
Unit Type of Package 1 | PCE | PCE | PCE |
Number of Units in Package 1 | 1 | 1 | 1 |
Package 1 Height | 16cm | 16cm | 16cm |
Package 1 Width | 17.7cm | 17.7cm | 17.7cm |
Package 1 Length | 27.5cm | 27.5cm | 27.5cm |
Package 1 Weight | 2813g | 2811.25g | 2846.25 g |
Unit Type of Package 2 | S03 | S03 | S03 |
Number of Units in Package 2 | 2 | 2 | 2 |
Package 2 Height | 30cm | 30cm | 30cm |
Package 2 Width | 30cm | 30cm | 30cm |
Package 2 Length | 40cm | 40cm | 40cm |
Package 2 Weight | 6.184 kg | 6.18kg | 6.25kg |
Unit Type of Package 3 | P06 | P06 | P06 |
Number of Units in Package 3 | 16 | 16 | 16 |
Package 3 Height | 75cm | 75cm | 75cm |
Package 3 Width | 60cm | 60cm | 60cm |
Package 3 Length | 80cm | 80cm | 80cm |
Package 3 Weight | 59.468 kg | 59.44 kg | 60kg |
contract warranty | |||
Warranty | 18 months | 18 months | 18 months |
Weight | N/A |
---|---|
Dimensions | N/A |
Related products
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details