Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my
Product Description
QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5 V DC … 56 V DC are covered.
Dimensions
Width |
70 mm |
Height |
130 mm |
Depth |
125 mm |
Installation dimensions |
Installation distance right/left |
5 mm / 5 mm |
Installation distance top/bottom |
50 mm / 50 mm |
Ambient Conditions
Degree of protection |
IP20 |
Ambient temperature (operation) |
-25 °C … 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) |
-40 °C … 85 °C |
Ambient temperature (start-up type tested) |
-40 °C |
Maximum altitude |
≤ 4000 m (> 2000 m, observe derating) |
Climatic class |
3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) |
5 Hz … 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C) |
Input Data
AC operation
Nominal input voltage range |
100 V AC … 240 V AC |
Input voltage range |
100 V AC … 240 V AC -10 % … +10 % |
Derating |
< 100 V AC (1 %/V) |
Electric strength, max. |
300 V AC 60 s |
Typical national grid voltage |
120 V AC |
230 V AC |
Voltage type of supply voltage |
AC |
Inrush current |
typ. 11 A (at 25 °C) |
Inrush current integral (I2t) |
< 0.3 A2s |
Inrush current limitation |
11 A |
AC frequency range |
50 Hz … 60 Hz -10 % … +10 % |
Frequency range (fN) |
50 Hz … 60 Hz -10 % … +10 % |
Mains buffering time |
typ. 37 ms (120 V AC) |
typ. 38 ms (230 V AC) |
Current consumption |
6.3 A (100 V AC) |
5 A (120 V AC) |
2.6 A (230 V AC) |
2.5 A (240 V AC) |
Nominal power consumption |
474 VA |
Protective circuit |
Transient surge protection; Varistor, gas-filled surge arrester |
Power factor (cos phi) |
0.94 |
Switch-on time |
< 1 s |
Typical response time |
300 ms (from SLEEP MODE) |
Input fuse |
12 A (slow-blow, internal) |
Recommended breaker for input protection |
10 A … 16 A (Characteristic B, C or comparable) |
Discharge current to PE |
< 3.5 mA |
0.7 mA (264 V AC, 60 Hz) |
DC operation
Nominal input voltage range |
110 V DC … 250 V DC |
Input voltage range |
110 V DC … 250 V DC -18 % … +40 % |
Derating |
< 110 V DC (1 %/V) |
Voltage type of supply voltage |
DC |
Current consumption |
5.6 A (110 V DC) |
2.3 A (250 V DC) |
Output Data
Efficiency |
typ. 93.5 % (120 V AC) |
typ. 94.7 % (230 V AC) |
Output characteristic |
U/I Advanced |
Smart HICCUP |
FUSE MODE |
Nominal output voltage |
110 V DC |
Setting range of the output voltage (USet) |
110 V DC … 135 V DC (constant capacity) |
Nominal output current (IN) |
4 A |
Static Boost (IStat.Boost) |
5 A |
Dynamic Boost (IDyn.Boost) |
6 A (5 s) |
Selective Fuse Breaking (ISFB) |
24 A (15 ms) |
Magnetic circuit breaker tripping |
A1 … A4 / B2 … B4 / C1 … C2 / Z1 … Z4 |
Derating |
> 60 °C … 70 °C (2.5%/K) |
Feedback voltage resistance |
≤ 160 V DC |
Protection against overvoltage at the output (OVP) |
< 150 V DC |
Control deviation |
< 0.5 % (Static load change 10 % … 90 %) |
< 4 % (Dynamic load change 10 % … 90 %, (10 Hz)) |
< 0.25 % (change in input voltage ±10 %) |
Residual ripple |
< 600 mVPP (with nominal values) |
Short-circuit-proof |
yes |
No-load proof |
yes |
Output power |
440 W |
550 W |
660 W |
Apparent power |
336 VA (120 V, UOUT = 24 V, IOUT = stat. Boost) |
345 VA (230 V, UOUT = 24 V, IOUT = stat. Boost) |
Maximum no-load power dissipation |
< 7 W (120 V AC) |
< 7 W (230 V AC) |
Power loss nominal load max. |
< 31 W (120 V AC) |
< 25 W (230 V AC) |
Power dissipation SLEEP MODE |
< 7 W (120 V AC) |
< 7 W (230 V AC) |
Crest factor |
typ. 1.54 (120 V AC) |
typ. 1.57 (230 V AC) |
Rise time |
< 1 s (UOut = 10 % … 90 %) |
Connection in parallel |
yes, for redundancy and increased capacity |
Connection in series |
yes |
Commercial Data
Item number |
2904613 |
Packing unit |
1 pc |
Minimum order quantity |
1 pc |
Product Key |
CMPI14 |
GTIN |
4063151023461 |
Weight per Piece (including packing) |
1,619 g |
Weight per Piece (excluding packing) |
1,265 g |
Customs tariff number |
85044083 |
Country of origin |
TH |
Standards and Regulations
Rail applications |
EN 50121-3-2 |
EN 50121-5 |
EN 50163 |
IEC 62236-3-2 |
IEC 62236-5 |
Standard – Limitation of mains harmonic currents |
EN 61000-3-2 |
Standard – Electrical safety |
IEC 61010-2-201 |
Standard – Safe isolation |
IEC 61010-2-201 |
Standard – safety for equipment for measurement, control, and laboratory use |
IEC 61010-1 |
Battery charging |
DIN 41773-1 |
Approval – requirement of the semiconductor industry with regard to mains voltage dips |
SEMI F47-0706, EN 61000-4-11 |
Overvoltage category |
EN 61010-1 |
II (≤ 4000 m) |
EN 62477-1 |
III (≤ 2000 m) |
Approval data
CSA |
CAN/CSA-C22.2 No. 61010-1-1 |
CAN/CSA-C22.2 No. 61010-1-12 |
Shipbuilding approval |
DNV GL applied for |
SIQ |
BG (type approved) |
CB-Scheme (IEC 61010-1, IEC 61010-2-201, IEC 60950-1) |
UL approvals |
UL Listed UL 61010-1 |
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) applied for |
EMC Data
Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
EMC requirements for noise immunity |
EN 61000-6-1 |
EN 61000-6-2 |
EMC requirements, power plant |
IEC 61850-3 |
EN 61000-6-5 |
Conducted noise emission |
EN 55016 |
EN 61000-6-3 (Class B) |
Interference emission |
Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) |
Noise emission |
Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) |
Noise emission |
EN 55016 |
EN 61000-6-3 (Class B) |
Noise immunity |
Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply) |
Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply) |
DNV GL conducted interference |
Class A |
Additional text |
Area power distribution |
DNV GL noise radiation |
Class B |
Additional text |
Bridge and deck area |