Pepperl+Fuchs NJ10-30GM-N Inductive Sensor

USD 80.00

Pepperl+Fuchs NJ10-30GM-N NAMUR inductive sensor with 10 mm flush sensing, SIL 2 capability, 2 m cable and IP66/IP67 rating.

SKU PEPPERL-FUCHS-NJ10-30GM-N Category
Top Brands > PEPPERL+FUCHS > PEPPERL+FUCHS Proximity Sensor

Pepperl+Fuchs NJ10-30GM-N Inductive Proximity Sensor

BrandPepperl+Fuchs
Model IdentifierNJ10-30GM-N
Official Part NumberNJ10-30GM-N

Technical Overview

The Pepperl+Fuchs NJ10-30GM-N is a cylindrical M30 inductive proximity sensor with a 10 mm rated flush operating distance and a NAMUR normally closed output. Its two-wire circuit operates at a nominal 8.2 V and accepts 5–25 V, with switching up to 300 Hz; the sensor uses a preassembled 2 m cable rather than an imaging or network interface. A stainless-steel housing, IP66/IP67 protection, and a -25 to 100 °C ambient range support industrial installation, while the manufacturer lists use up to SIL 2.

M30 flush-mounted NAMUR inductive sensor with 10 mm rated sensing, a 2 m cable, SIL 2 capability, and IP66/IP67 protection.

Key Features

  • Inductive sensing element; no imaging silicon or pixel array
  • 10 mm rated operating distance; assured operating distance 0–8.1 mm
  • Non-imaging inductive detection; shutter mechanism is not applicable
  • Two-wire NAMUR output, normally closed, operating at nominal 8.2 V
  • Switching frequency up to 300 Hz; no onboard processor or AI acceleration specified
  • M30 x 1.5 threaded cylindrical body for flush installation; no lens interface
  • Preassembled 2 m, 2-core PVC cable; sensor output is NAMUR rather than a multi-pin plug
  • No image buffer or memory is used in this inductive sensor
  • Manufacturer product page lists the model in stock; SIL 2-capable application per IEC 61508

Flush M30 installation combines a 10 mm rated sensing distance with NAMUR output and SIL 2 capability.

Technical Specification Matrix

ParameterValue
SensorInductive proximity sensor; non-imaging
ShutterNot applicable; inductive sensing principle
ResolutionRated operating distance 10 mm; assured operating distance 0–8.1 mm
Pixel sizeNot applicable; no image sensor
Optical sensor classNot applicable; inductive sensor
Optical sensor sizeNot applicable; inductive sensor
Frame rateNot applicable; switching frequency 0–300 Hz
Exposure timeNot applicable; non-imaging sensor
Power consumptionNot separately specified; current consumption ≥3 mA with target absent and ≤1 mA with target present at nominal voltage
Power supplyNominal 8.2 V DC (internal resistance approx. 1 kΩ); operating voltage 5–25 V
Image memoryNot applicable; no image memory
Operating temperature-25 to 100 °C
Storage temperatureNot specified in the product datasheet
Relative humidityNot specified in the product datasheet
InterfaceTwo-wire NAMUR output; normally closed; 0–300 Hz
I/O connectorPreassembled 2 m PVC cable, 2-wire (brown and blue); 0.75 mm² conductor cross-section
Lens mountNot applicable; M30 x 1.5 threaded sensor body, flush installation
IP ratingIP66 / IP67
Housing materialStainless steel 1.4305 / AISI 303; PBT sensing face
Physical Weight (kg)0.210
Dimensions L x W x H (cm)4.0 x 3.0 x 3.0

Suggested applications

Engineering suggestions require suitability checks for your installation.

1. Flush metal-part position sensing

A machine station may need to confirm a steel fixture or component is seated at a repeatable point without a protruding sensor face.

Potential use

The flush-mounted M30 inductive sensor detects metal targets at a 10 mm rated distance and provides a normally closed NAMUR signal for a compatible switching amplifier or intrinsically safe input. Verify target material, assured range, and interface compatibility in the final design.

10 mm rated distance Flush M30 NAMUR IP66/IP67

2. Hazardous-area machine status input

A process machine may require non-contact position feedback near an installation subject to hazardous-area and functional-safety design constraints.

Potential use

The manufacturer lists SIL 2 use and relevant approvals for the sensor variant; its NAMUR circuit can feed an appropriately selected safety or isolated input. Validate the full certificate conditions, installation, and system-level safety calculation before use.

SIL 2 capable NAMUR 2-wire Stainless steel -25 to 100 °C